Evaluation of Plastic Pipe Fittings used in Duct Systems
SGS U.S. Testing Company Inc.
SGS U.S. Testing Company Inc.
1341 North 108th East Avenue
Tel: 918-437-8333
Fax: 918-437-8487
July 9, 1998
Report Number: 109962-1
|
|
CLIENT:
|
JB Engineering & Code Consulting
|
1661 Cardinal Drive
|
Munster, IN 46321
|
|
Attn: Julius Ballanco
|
SUBJECT:
|
Evaluation of Plastic Pipe Fittings used in Duct Systems.
|
SAMPLE ID:
|
19 plastic pipe fittings were received from the client on 5/28/98. The samples were received in good condition.
|
PROCEDURE:
|
The fittings were evaluated in accordance with ASTM D 2665-97, Section 6.3.2. The fittings were loaded with 750lbf/ft of centerline length. The fittings were then checked for cracking or any other signs of failure.
|
TEST DATE:
|
6/29/1998
|
RESULTS:
|
The test data and results are on the following page.
|
CONCLUSION:
|
The fittings do comply with the requirements of ASTM D 2665-97, Section 6.3.2 (which exceeds ASTM D 2412).
|
CERTIFICATION:
|
The tests reported here were conducted under the continuous, direct supervision of SGS U.S. Testing Company Inc., Tulsa, OK.
|
Signed for the Company

Jeff Simmons Dept. Manager/Product Evaluation
RESULTS:
Specimen
|
Load, lbf/ft
|
Failure
|
16" 45º Elbow
|
750
|
None
|
16"-14" Concentric Reducer
|
750
|
None
|
16" End Cap
|
750
|
None
|
14" Starting Collar
|
750
|
None
|
14"-12" Concentric Reducer
|
750
|
None
|
12" End Cap
|
750
|
None
|
10" End Cap
|
750
|
None
|
10" Coupling
|
750
|
None
|
8" 45º Elbow
|
750
|
None
|
8" 90º Elbow
|
750
|
None
|
6" Coupling
|
750
|
None
|
6" Starting Collar
|
750
|
None
|
6"-4" Concentric Reducer
|
750
|
None
|
6" 90º Black Max Elbow
|
750
|
None
|
4" Starting Collar
|
750
|
None
|
4"-14"-8" Black Max Boot Box
|
750
|
None
|
4"-12"-6" Black Max Boot Box
|
750
|
None
|
4"-10"-6" Black Max Boot Box
|
750
|
None
|
4"-10"-4" Black Max Boot Box
|
750
|
None
|